HBA - heated blower desiccant dryers

This type of dryer does not divert dried compressed air from the air system to remove moisture from the desiccant in an off-line tank. For regeneration, it uses its own high-performance centrifugal blower to direct ambient air through a heater and then through an off-line tank. There, the heated air stream regenerates the desiccant. Heated blower technology requires the largest initial capital investment, but by diverting compressed air from the system for regeneration, it offers significantly lower operating costs than other dryer technologies.

Standard reference conditions

  • Working/regeneration cycle: 240/240 min
  • Working pressure: 7 bar (max. 10 bar)
  • PDP 7 bar pressure: -40 ° C, CLASSS2 - ISO 8573-1
  • Inlet air temperature 35° C (max. 50°C)
  • Regeneration cycle 240/240 min.

 

Type Flow rate (m3/h) Max. pressure Heating power consumption Blower power consumption BSP Data   Type Flow rate (m3/h) Max. pressure Heating power consumption Blower power consumption BSP Data
HBA 500 500 10 6 1,5 2" pdf   HBA 3900 3900 10 45 11 DN 100 pdf
HBA 900 900 10 12 2,2 2" pdf   HBA 5300 5300 10 60 15 DN 150 pdf
HBA 1400 1400 10 18 5,5 3" pdf   HBA 7000 7000 10 80 30 DN 150 pdf
HBA 1800 1800 10 24 4 3" pdf   HBA 9300 9300 10 100 37 DN 150 pdf
HBA 2200 2200 10 24 5,5 3" pdf   HBA 10600 10600 10 125 37 DN 150 pdf
HBA 2600 2600 10 30 7,5 3" pdf   HBA 14900 14900 10 175 55 DN 200 pdf
HBA 3200 3200 10 36 9,2 DN 100 pdf  